Safety:
Temporary personal protective equipment is designed for one purpose only, to protect the worker.
Grounding equipment should be manufactured to and maintained to the highest standards.
Standards:
Very stringent requirements are specified by the ASTM F855 standard. While this is a voluntary
standard, we design all our clamps, cables and ferrules to exceed the values of this standard.
The withstand values from ASTM are:
Grade 15 Cycle
(kA)
30 Cycle
(kA)
Cable Size
(Copper)
Continuous
Current
Rating
A RMS
1 14 10 #2 200
2 21 15 1/0 250
3 27 20 2/0 300
4 34 25 3/0 350
5 43 30 4/0 400
Quality:
Whether it’s the machining of the casting, the assembly of the clamp, or the assembly of the complete
grounding or jumper assembly, we pride ourselves in the quality of the product that is created at Hast-
ings. Every employee that handles the parts is vigilant for any quality issues.
Material:
Clamps are available in either bronze alloy or aluminum alloy metals. Great care is taken in selecting the
best materials for the performance required. The bronze alloys allow for higher strength and higher melt-
ing temperatures. Aluminum alloys allow for lighter weight and less resistance.
Experience:
Hastings works closely with the utility industry in solving grounding problems. Through our close con-
tact with our customers, we stay in touch with their needs and this guides our efforts for future product
designs. Hastings also participates in the development of industry standards.
SUBSTATION GROUNDING SET AND GROUND LIFTING TOOL
? The below listed tools enable operating personnel the capability of grounding de-energized substations safely and easily with use of the ground lifting tool.
? Two ranges of ground clamps, both have bolted type pressure terminals.
? Ground clamps are mounted on an 1 1/4” X 8’ fiberglass pole. The bottom end of the clamp mounted pole has a fiberglass male splice to allow extension sections to be added to meet the required height for applying the ground set.
? The ground lifting tool has a universal end and is supplied with a large opening “C” hook that is coated for protection. It comes complete with handline block, adjustable block clamp and 50’ of 3/8” polypropylene rope. The hook and block clamp are mounted on an 8’ fiberglass pole with a male splice on the bottom end to allow additional lengths of extensions to be added as required.
CAT NO DESCRIPTION MAIN LINE
RANGE
MAXIMUM
MAIN LINE
RANGE
MINIMUM
MAXIMUM
CABLE
SIZE
MAXIMUM FAULT
CURRENT RATING
LBS
13761 GROUND CLAMP MOUNTED
ON 8’ FIBERGLASS POLE WITH
MALE SPLICE ON BOTTOM END
3” DIA BUS? OR CABLE
6 STR? 18 DIA
4/0 54KA@ 15 CYCLES
39KA@ 30 CYCLES? 7.2
13762 GROUND CLAMP MOUNTED
ON 8’ FIBERGLASS POLE WITH
MALE SPLICE ON BOTTOM END
6.625 DIA BUS
1/0 STR .398 DIA
4/0 54KA@ 15 CYCLES
39KA@ 30 CYCLES? 8.5
13763 GROUND LIFTING TOOL COMPLETE WITH “C” HOOK, HANDLINE BLOCK AND CLAMP, 50’ OF
3/8” POLYPROPYLENE ROPE INSTALLED ON A 8’ FIBERGLASS POLE WITH MALE SPLICE AT
BOTTOM END? 8.0
NOTE: 1 1/4” EXTENSION AND BASE SECTIONS CAN BE ADDED FOR ADDITIONAL LENGTHS, SEE PAGE 107