Safety:
Temporary personal protective equipment is designed for one purpose only, to protect the worker.
Grounding equipment should be manufactured to and maintained to the highest standards.
Standards:
Very stringent requirements are specified by the ASTM F855 standard. While this is a voluntary
standard, we design all our clamps, cables and ferrules to exceed the values of this standard.
The withstand values from ASTM are:
Grade 15 Cycle
(kA)
30 Cycle
(kA)
Cable Size
(Copper)
Continuous
Current
Rating
A RMS
1 14 10 #2 200
2 21 15 1/0 250
3 27 20 2/0 300
4 34 25 3/0 350
5 43 30 4/0 400
Quality:
Whether it’s the machining of the casting, the assembly of the clamp, or the assembly of the complete
grounding or jumper assembly, we pride ourselves in the quality of the product that is created at Hast-
ings. Every employee that handles the parts is vigilant for any quality issues.
Material:
Clamps are available in either bronze alloy or aluminum alloy metals. Great care is taken in selecting the
best materials for the performance required. The bronze alloys allow for higher strength and higher melt-
ing temperatures. Aluminum alloys allow for lighter weight and less resistance.
Experience:
Hastings works closely with the utility industry in solving grounding problems. Through our close con-
tact with our customers, we stay in touch with their needs and this guides our efforts for future product
designs. Hastings also participates in the development of industry standards.
GROUNDING CABLE FERRULES
FERRULE FOR BOLTED TYPE TERMINALS
CAT NO SIZE AWG LBS
11656 #2 0.1
11657 1/0 0.1
11658 2/0 0.1
11660 4/0 0.1
FERRULE FOR THREADED TYPE TERMINALS, 5/8-11 NC
CAT NO SIZE AWG LBS
12998 #2 0.3
12999 1/0 0.3
13000 2/0 0.3
13001 4/0 0.4
P50349 5” LONG HEAT SHRINK 0.1
FERRULE FOR COMPRESSION-BOLTED TYPE TERMINALS
CAT NO SIZE AWG LBS
P30244 #2 0.3
P30245 1/0 0.4
P30246 2/0 0.4
P30247 4/0 0.5
FACTORY INSTALLED FERRULES –
COMPRESSION BOLTED TYPE
CAT NO SIZE AWG LBS
6756 #2 1.0
6757 1/0 1.0
6758 2/0 1.0
6759 4/0 1.0
FACTORY INSTALLED FERRULES –
COMPRESSION 5/8-11 NC THREADED TYPE
CAT NO SIZE AWG LBS
6760 #2 1.0
6761 1/0 1.0
6762 2/0 1.0
6763 4/0 1.0
FERRULES WITH FACTORY APPLIED CLEAR HEAT SHRINK
? Provides positive stress relief of grounding cables at their terminations
? Clear heat shrink allows visual inspection of cable strands and termination
? Heat shrink materials provides a barrier to resist moisture and corrosion at the termination
FERRULE FOR ELBOWS – URD
CAT NO SIZE AWG LBS
P30916 1/0 0.4
P30917 2/0 0.5